PRODUCTS

3RW4436-6BC35

Product description:

Packaging dimensions (L x W x H)
431,00 x 351,00 x 384,00 mm
Net weight
11,89 Kg

Product introduction

General technical data

product brand name
SIRIUS
product designation
Soft starter
product feature

● integrated bypass contact system
Yes
● thyristors
Yes
product function

● intrinsic device protection
Yes
● motor overload protection
Yes
● evaluation of thermistor motor protection
Yes
● external reset
Yes
● adjustable current limitation
Yes
● inside-delta circuit
Yes
product component motor brake output
Yes
insulation voltage rated valueV690
degree of pollution
3, acc. to IEC 60947-4-2
reference code according to EN 61346-2
Q
reference code according to DIN 40719 extended according to IEC 204-2 according to IEC 750
G


Power Electronics

operational current

● at 40 °C rated valueA432
● at 50 °C rated valueA385
● at 60 °C rated valueA335
operational current for 3-phase motors at inside-delta circuit

● at 40 °C rated valueA748
● at 50 °C rated valueA667
● at 60 °C rated valueA580
yielded mechanical performance for 3-phase motors

● at 400 V

— at standard circuit at 40 °C rated valuekW250
— at inside-delta circuit at 40 °C rated valuekW400
● at 500 V

— at standard circuit at 40 °C rated valuekW315
— at inside-delta circuit at 40 °C rated valuekW500
operating frequency rated valueHz50 ... 60
relative negative tolerance of the operating frequency%-10
relative positive tolerance of the operating frequency%10
operating voltage at standard circuit rated valueV400 ... 600
relative negative tolerance of the operating voltage at standard circuit%-15
relative positive tolerance of the operating voltage at standard circuit%10
operating voltage at inside-delta circuit rated valueV400 ... 600
relative negative tolerance of the operating voltage at inside-delta circuit%-15
relative positive tolerance of the operating voltage at inside-delta circuit%10
minimum load [%]%8
adjustable motor current for motor overload protection minimum rated valueA86
continuous operating current [% of Ie] at 40 °C%115
power loss [W] at operational current at 40 °C during operation typicalW232


Control circuit/ Control


type of voltage of the control supply voltage
AC
control supply voltage frequency 1 rated valueHz50
control supply voltage frequency 2 rated valueHz60
relative negative tolerance of the control supply voltage frequency%-10
relative positive tolerance of the control supply voltage frequency%10
control supply voltage 1 at AC

● at 50 Hz rated valueV115
● at 60 Hz rated valueV115
relative negative tolerance of the control supply voltage at AC at 50 Hz%-15
relative positive tolerance of the control supply voltage at AC at 50 Hz%10
relative negative tolerance of the control supply voltage at AC at 60 Hz%-15
relative positive tolerance of the control supply voltage at AC at 60 Hz%10
display version for fault signal
Display


Mechanical data

widthmm210
heightmm230
depthmm298
fastening method
screw fixing
mounting position
with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back
required spacing with side-by-side mounting

● upwardsmm100
● at the sidemm5
● downwardsmm75
wire length maximumm500
number of poles for main current circuit
3


Connections/ Terminals

type of electrical connection

● for main current circuit
busbar connection
● for auxiliary and control circuit
screw-type terminals
number of NC contacts for auxiliary contacts
0
number of NO contacts for auxiliary contacts
3
number of CO contacts for auxiliary contacts
1
type of connectable conductor cross-sections for main contacts for box terminal using the front clamping point

● finely stranded with core end processing
70 ... 240 mm²
● finely stranded without core end processing
70 ... 240 mm²
● stranded
95 ... 300 mm²
type of connectable conductor cross-sections for main contacts for box terminal using the back clamping point

● finely stranded with core end processing
120 ... 185 mm²
● finely stranded without core end processing
120 ... 185 mm²
● stranded
120 ... 240 mm²
type of connectable conductor cross-sections for main contacts for box terminal using both clamping points

● finely stranded with core end processing
min. 2x 50 mm², max. 2x 185 mm²
● finely stranded without core end processing
min. 2x 50 mm², max. 2x 185 mm²
● stranded
max. 2x 70 mm², max. 2x 240 mm²
type of connectable conductor cross-sections for AWG cables for main contacts for box terminal

● using the back clamping point
250 ... 500 kcmil
● using the front clamping point
3/0 ... 600 kcmil
● using both clamping points
min. 2x 2/0, max. 2x 500 kcmil
type of connectable conductor cross-sections for DIN cable lug for main contacts

● finely stranded
50 ... 240 mm²
● stranded
70 ... 240 mm²
type of connectable conductor cross-sections for auxiliary contacts

● solid
2x (0.5 ... 2.5 mm²)
● finely stranded with core end processing
2x (0.5 ... 1.5 mm²)
type of connectable conductor cross-sections for AWG cables

● for main contacts
2/0 ... 500 kcmil
● for auxiliary contacts
2x (20 ... 14)
● for auxiliary contacts finely stranded with core end processing
2x (20 ... 16)


Ambient conditions

installation altitude at height above sea levelm5 000
environmental category

● during transport according to IEC 60721
2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
● during storage according to IEC 60721
1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4
● during operation according to IEC 60721
3K6 (no formation of ice, no condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
ambient temperature

● during operation°C60
● during storage°C-25 ... +80
derating temperature°C40
protection class IP on the front according to IEC 60529
IP00; IP20 with box terminal/cover
touch protection on the front according to IEC 60529
finger-safe, for vertical contact from the front with box terminal/cover


UL/CSA ratings

yielded mechanical performance [hp] for 3-phase AC motor

● at 460/480 V

— at standard circuit at 50 °C rated valuehp300
— at inside-delta circuit at 50 °C rated valuehp600
● at 575/600 V

— at standard circuit at 50 °C rated valuehp400
— at inside-delta circuit at 50 °C rated valuehp750
contact rating of auxiliary contacts according to UL
B300 / R300


1

Shipping Method:

2
Previous:3RW4427-1BC35

Leave a message

Submit